4000A data center switchgear built for high-density halls: 4000A main, 100kA bracing, main-tie-main configuration and drawout breakers.
A single 4000A service at 480Y/277V carries roughly 3,300 kVA. That is one large hall or two medium ones, and it is the size where switchboards stop being practical and drawout switchgear takes over: breakers get heavy, fault current climbs past 65kA, and maintenance has to happen without dropping the bus.
We build 4000A lineups as UL 1558 switchgear with drawout low-voltage power breakers, compartmented sections and a main-tie-main arrangement so either feed can be isolated while the hall stays energized.
Bus is silver-plated copper braced for 100kA. Sections run about 132 inches wide each, 90 inches tall and 30 inches deep before you add the utility compartment or a metering section. A typical main-tie-main lineup lands as five to seven sections and ships split.
Cable entry is usually bottom for the utility feeders and top for the distribution leaving the room. We confirm both against the room drawing because reversing entry after fabrication means a field cut that voids the listing.
Typically five to seven, depending on metering, tie breaker and the number of distribution sections.
Yes. That is the purpose of the main-tie-main arrangement and the interlock scheme.