White space power distribution: from the service entrance to the rack row, including distribution switchboards, remote power panels and busway.
White space power starts at the service entrance and ends at the rack PDU. Between those two points sit distribution switchboards, remote power panels, busway tap boxes and the branch circuits that feed each cabinet row.
Each step is a place where capacity gets stranded. A 4000A service feeding 800A distribution boards that feed 400A RPPs can lose a third of its usable capacity to oversized breakers and undersized neutrals if nobody does the arithmetic.
Row density drives the RPP size. A 225A RPP serves a light row; a 400A or 600A panel serves high-density cabinets. Busway makes sense where rows will be reconfigured; hard-wired panels make sense where the layout is fixed.
Neutral sizing matters more than most people expect. Modern server loads produce harmonic current on the neutral, so a 400A panel with a 400A neutral can run hot. We build with oversized neutrals where the load profile calls for it.
Send your single-line or tell us the service size. We reply with pricing, lead time and a drawing schedule.